XLPE Insulated, LSZH Sheathed And Overall Screened Instrumentation Cables (Single Triple)

Original
price: Negotiable
minimum:
Total supply:
Delivery term: The date of payment from buyers deliver within days
seat: Shandong
Validity to: Long-term effective
Last update: 2017-12-08 16:19
Browse the number: 257
inquiry
Company Profile
 
 
Product details

Supplying you with customized xlpe insulated, lszh sheathed and overall screened instrumentation cables (single triple), it is one of the reliable xlpe insulated, lszh sheathed and overall screened instrumentation cables (single triple) manufacturers and suppliers, welcome to wholesale our products at good price from our factory.

XLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Single Triple)

RE-2X(St)H 90°C / 300 V

STANDARDS

Basic design to EN 50288-7

APPLICATION

Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations.

FIRE PERFORMANCE

Flame Retardance (Single Vertical

Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE

0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation

(Vertically-mounted bundled wires

& cable test)***

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance**

ICEA S-73-532

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION


Conductor:

Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation:

Extruded cross-linked XLPE compound, EN 50290. 2-29.

Triple:

Three conductors twisted to form a triple

Lay-up:

Triples laid up in layers of optimum pitch

Separator:

Polyester tape

Overall Screen:

Aluminium/polyester tape with tinned copper drain wire, 0.5mm2

Outer Sheath:

Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE


Insulation:

Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.

Outer Sheath:

Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES


Temperature Range During Operation (Fixed State):

-30°C – +90°C

Temperature Range During Installation (Mobile State):

-5°C – +50°C

Minimum Bending Radius:

7.5 X Overall Diameter

CONSTRUCTION PARAMETERS

Cable

Code

RE-2X(St)YH

No. of Triples x3xCross

Section

Nominal

Insulation

Thickness

Nominal

Outer Sheath

Thickness

Nominal

Overall

Diameter

Approx. Weight


No.x3xmm2

mm

mm

mm

kg/km

RE-2X(St)H 1T0.5

1x3x0,50

0.35

0.8

5.4

45

RE-2X(St)H 1T0.75

1x3x0,75

0.38

0.9

6.1

59

RE-2X(St)H 1T1.0

1x3x1.0

0.4

0.9

6.6

66

RE-2X(St)H 1T1.3

1x3x1,3

0.45

0.9

7.2

86

RE-2X(St)H 1T1.5

1x3x1,5

0.45

0.9

7.5

95

Note : Other conductor sizes & core configurations are available upon request.

Electrical PROPERTIES

Conductor Area Size

mm 2

0.5

0.75

1.0

1.3

1.5

Insulation thickness (nominal)

mm

0.35

0.38

0.4

0.45

0.45

Conductor resistance (20°C)

Ω/km

36.7

25.0

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

5000

5000

5000

5000

Mutual Capacitance (1 kHz)

pF/m(Max.)

115

Inductance

mH/km(Max.)

1

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Operating voltage

V

300

Test Voltage Urms

Core to Core

V

1500

Core to Screen

V

1500


Total0bar [View All]  Related Comments
 